3 Operation and Test Run
3 - 6
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
This section explains how to use the Digital Operator keys in a typical operation (when the Display
Selection is “Complete display”) and in the extended function mode U as operation examples.
This operation will be the same even if you select a different setting in the Display Mode (b037),
although the number of parameters that you will see on the display differs.
Precautions for Correct UsePrecautions for Correct Use
• You can change the parameter display on the Digital Operator by the Display Selection (b037).
For details, refer to Display Selection on page 7-78.
• In the 3G3RX-V1, the factory setting for the Display Selection (b037) is “Complete display,”
which was changed from the conventional default “Basic display.” You can see and set all
parameters when you turn on the power supply for the first time.
• You can set the initial screen displayed after turning on the power supply by the Initial Screen
Selection (b038). For details, refer to Initial Screen Selection (Initial Screen after Power-on) on
page 7-81.
• You can display only the parameters registered as user parameters. It is also possible to
automatically register changed parameters, or directly set specific parameters. For details,
refer to User Parameter Automatic Setting Function on page 7-81.
Regardless of the display mode of the Digital Operator, if you press the Mode key for 3 seconds
or more, the data of Output Frequency Monitor (d001) is displayed. However, the Digital Operator
continues to display the function group parameters in sequence as the normal operation if you
press the Mode key for less than 3 seconds. (Example: A001 → F001 → b001 → C001 ... (after
3 s) “500” appears)
3-1-2 Key Operation Method
Item Parameter No. Data Description
Display Selection b037
00 Complete display (Factory setting)
01 Individual display of functions
02 User setting
03 Data comparison display
04 Basic display
Initial Screen
Selection (Initial
screen after
power-on)
b038
000 Screen on which the Enter key is pressed last
001 to 060 d001 to d060 (001: Factory setting)
201 F001
202 Do not set.
User Parameter
Automatic Setting
Function
b039
00 Disabled (Factory setting)
01 Enabled