EasyManua.ls Logo

Omron RX Series - I;O Voltage;Current;Electric Power Measurement Method

Omron RX Series
688 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11 Maintenance and Inspection
11 - 12
High-function General-purpose Inverter 3G3RX-V1 User's Manual (SBCE-367)
Measuring instruments commonly used for input/output voltage, current, or electric power
measurement are shown below.
11-3-4 I/O Voltage/Current/Electric Power Measurement Method
Measurement
item
Measurement point
Measuring
instrument
Remarks Measurement value reference
Power
supply
voltage E
IN
Between R/L1 and S/L2
(ER)
Between S/L2 and T/L3
(ER)
Between T/L3 and R/L1
(ER)
Moving-iron
voltmeter
or
rectifier type
voltmeter
All
effective
values
200-V class: 200 to 240 V, 50/60 Hz
400-V class: 380 to 480 V, 50/60 Hz
Power
supply
current I
IN
Current in R/L1, S/L2
T/L3: (I
R), (IS), (IT)
Moving iron
ammeter
All
effective
values
When input current is not balanced:
I
IN = (IR + IS + IT) / 3
Input
electric
power W
IN
Between R/L1 and S/L2
(W
I1)
Between S/L2 and T/L3
(W
I2)
Between T/L3 and R/L1
(W
I3)
Electrodynamic
wattmeter
All
effective
values
Three-wattmeter method
(W
I1) + (WI2) + (WI3)
Input power
factor PfIN
Calculate this from the measured values of power supply
voltage E
IN, power supply current IIN, and input electric
power W
IN.
Output
voltage
E
OUT
Between U/T1 and V/T2
(EU)
Between V/T2 and W/T3
(EV)
Between W/T3 and U/T1
(E
W)
Refer to the figure
on the next page.
or
rectifier type
voltmeter
Effective
value of
fundamental
wave
I R
I S
I T
ER
ET
ES
WI2
WI3
WI1
R
/
L1
U
/
T1
V
/
T2
W
/
T3
T
/
L3
S
/
L2
U
V
W
I U
I V
I W
EU
EW
EV
WO2
WO1
Motor
W
V
U R
S
T
Power
supply
Inverter
PfIN
=
W
IN
3 · EIN · IIN
×100 [%]

Table of Contents