• Set the response time for each multi-function input S1 to S8 terminal and the forward RUN command
terminal FW independently.
This function is effective for removing noise caused by chattering etc.
• If stable terminal input is not possible due to chattering, increase the set value.
However, increasing the set value results in a slow response. The setting range is 0 to 200, which
provides a response time of approximately 2 to 400 ms.
• The digital terminal MP on the control circuit terminal block enables the monitoring of the output
frequency and the output current.
• The terminal MP provides 10-VDC pulse output or PWM output.
• Select the signal you want to output from the following table.
• When this parameter is set to 03 (Digital output frequency) or 08 (Digital current monitor), the
terminal provides pulse output.
• For pulse output signals, use a digital frequency counter.
For other output signals, use an analog meter.
Input Terminal Response Time
Parameter
No.
Function name Data
Default
data
Unit
C160 to
C167
Multi-function Input S1 to S8
Response Time
0. to 200. (x 2 ms)
*1
*1. When 0 is set, the response time is 2 ms.
1. ms
C168
Forward RUN Command FW
Response Time
Digital MP Terminal
MP Selection
Parameter No. Data Description
PWM/
pulse
Full-scale value
C027
00
Output frequency
*1
PWM
0 to Maximum frequency [Hz]
*2
01 Output current PWM 0% to 200%
02
Output torque (Only in the heavy load
mode)
*3
PWM 0% to 200%
03
Digital output frequency
*4
pulse 0 to Maximum frequency [Hz]
04 Output voltage PWM 0% to 100%
05 Input power PWM 0% to 200%
06 Electronic thermal load rate PWM 0% to 100%
07
LAD frequency
*1
PWM 0 to Maximum frequency [Hz]
08 Digital current monitor pulse
*5
09 Motor temperature PWM
0 to 200°C (0°C output at 0°C or
lower)
10 Cooling fin temperature PWM
0 to 200°C (0°C output at 0°C or
lower)
12
DriveProgramming (YA(0))
*6
PWM 0% to 100%
19 Option 1 PWM –
20 Option 2 PWM –