7 - 139
7 Detailed Functions
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
7-5 Multi-function Terminal Functions (Group C)
7
Each multi-function output terminal can be allocated with the ON/OFF delay time.
All output signals turn ON/OFF immediately when the set conditions are satisfied.
However, depending on the selected signal, chattering may occur. In such a case, use this function to
hold or delay the signal.
Set the ON/OFF delay parameter for a total of the six output terminals: multi-function output terminals
P1 to P5 and one relay output (MA, MB) terminal.
The correspondence between each output terminal and the related ON/OFF delay parameter is
shown in the table below.
Multi-function Output ON/OFF Delay Time
Output terminal ON delay time OFF delay time
P1 C130 C131
P2 C132 C133
P3 C134 C135
P4 C136 C137
P5 C138 C139
Relay (MA, MB) C140 C141
Parameter
No.
Function name Data
Default
data
Unit
C130
Multi-function Output P1 ON
Delay Time
0.0 to 100.0 0.0 s
C132
Multi-function Output P2 ON
Delay Time
C134
Multi-function Output P3 ON
Delay Time
C136
Multi-function Output P4 ON
Delay Time
C138
Multi-function Output P5 ON
Delay Time
C140
Multi-function Relay Output ON
Delay Time
C131
Multi-function Output P1 OFF
Delay Time
0.0 to 100.0 0.0 s
C133
Multi-function Output P2 OFF
Delay Time
C135
Multi-function Output P3 OFF
Delay Time
C137
Multi-function Output P4 OFF
Delay Time
C139
Multi-function Output P5 OFF
Delay Time
C141
Multi-function Relay Output OFF
Delay Time