12 Options
12 - 28
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
• These terminals are used to connect the optional DC reactor for power factor improvement.
By factory setting, a short-circuit bar is connected between the terminals +1 and –P/+2. Before
connecting the DC reactor, remove this short-circuit bar.
• The length of the DC reactor connection cable must be 5 m or shorter.
• The DC reactor has no polarity.
Remove the short-circuit bar only if you connect the DC reactor for use.
If you remove the short-circuit bar with the DC reactor unconnected, the inverter cannot operate
because no power is supplied to its main circuit.
12-5-3 Connection Examples
DC Reactor Connection Terminals (+1, P/+2)