High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
These terminals are used to connect the optional DC reactor for power factor improvement.
By factory setting, a short-circuit bar is connected between the terminals +1 and –P/+2. Before
connecting the DC reactor, remove this short-circuit bar.
The length of the DC reactor connection cable must be 5 m or shorter.
The DC reactor has no polarity.
Precautions for Correct UsePrecautions for Correct Use
Remove the short-circuit bar only if you connect the DC reactor for use.
If you remove the short-circuit bar with the DC reactor unconnected, the inverter cannot operate
because no power is supplied to its main circuit.
12-5-3 Connection Examples
DC Reactor Connection Terminals (+1, P/+2)
P/+2
M
+1
DC reactor
(option)
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
3-phase 200 VAC
3-phase 400 VAC
Power
supply
MC
MCCB
PD
P