6 - 5
6 Vector Control
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
6-2 Sensorless Vector Control
6
6-2-3 Auto-tuning of Motor Parameters
• Use this function to measure and automatically set the motor parameters required for the sensorless
vector control, 0-Hz sensorless vector control, or sensor vector control.
• To use the sensorless vector control, 0-Hz sensorless vector control, or sensor vector control
method, perform offline auto-tuning to measure the motor parameter values.
• The offline auto-tuning function is applicable to the 1st and 2nd control methods only. It cannot be
used for the 3rd control method.
• The measured motor parameter values will be set as 50-Hz data for one phase in 3-phase
Y-connection.
Parameter
No.
Function name Data Default data Unit
A044/A244
1st/2nd Control Method
*1
*1. To enable the switching to the 2nd control, allocate one of the Multi-function Input S1 to S8 Selection (C001 to
C008) to 08 (SET) and turn ON that terminal.
04: 0-Hz sensorless vector control 00 –
H003/H203 1st/2nd Motor Capacity
0.2/0.4/0.55/0.75/1.1/1.5/2.2/3.0/3.7/4.0/
5.5/7.5/11.0/15.0/18.5/22/30/37/45/55/
75/90/110/132
Maximum
applicable
motor capacity
kW
H004/H204
1st/2nd Motor Pole
Number
2/4/6/8/10 4 pole
A003/A203 1st/2nd Base Frequency
30. to 1st/2nd Maximum Frequency
(A004/A204)
60 Hz
A082
Motor Rated Voltage
Selection
200-V class: 200 V/215 V/220 V/230 V/
240 V
200 V
400-V class: 380 V/400 V/415 V/440 V/
460 V/480 V
400 V
b049
Heavy Load/Light Load
Selection
00: Heavy load mode (CT)
01: Light load mode (VT)
00
H060/H260 1st/2 Limit at 0 Hz 0.0 to 100.0 100.0
%
H061/H261
1st/2nd Boost Amount at
SLV Startup, 0 Hz
0. to 50. 50.
6-2-3 Auto-tuning of Motor Parameters
Parameter
No.
Function name Data Default data Unit
H001 Auto-tuning Selection
00: Disabled
01: Enabled (No motor rotation)
02: Enabled (Motor rotation)
00 –
H002/H202
1st/2nd Motor Parameter
selection
00: Standard motor parameter
01: Auto-tuning
02: Auto-tuning (Online auto-tuning
enabled)
00 –
H003/H203 1st/2nd Motor Capacity
0.1/0.2/0.4/0.55/0.75/1.1/1.5/2.2/3.0/3.7/
4.0/5.5/7.5/11.0/15.0/18.5/22/30/37/45/
55/75/90/110/132
Maximum
applicable
motor capacity
kW
H004/H204
1st/2nd Motor Pole
Number
2/4/6/8/10 4 pole