7 Detailed Functions
7 - 96
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
Precautions for Correct UsePrecautions for Correct Use
As a measure to prevent inadvertent parameter initialization, the Initialization Selection (b084)
and Initialization Execution (b180) settings are designed to be reset to 00 when the
initialization is completed or after power cycle. Be sure to set these parameters each time
when you need to initialize the parameter settings.
The following parameters are not initialized: the settings of the DriveProgramming User
Parameters U00 to U31 (P100 to P131), Total RUN Time Monitor (d016), Total Power ON Time
Monitor (d017), Initialization Data Selection (b085), Heavy Load/Light Load Selection (b049),
Thermistor Adjustment (C085), and analog adjustment parameters (C081 to C083, C121 to
C123).
Remember that you cannot restore the initialized data to the previous settings once you
execute parameter initialization.
Initializing the Parameter Settings (Clear Fault Monitor + Initialize Data +
Clear DriveProgramming)
Clearing Fault Monitor Methods
Step3:
Step1: Step2:
Initializing
Initialization
completes.
Press the Enter key to
set b084 to “04” .
Press the Enter key to
set b180 to “01” .
Initialization is completed
when the initialization
display disappears.
Step3:
Step1: Step2:
Clearing
Clear
completes.
Press the Enter key to
set b084 to “01” .
Press the Enter key to
set b180 to “01” .
Clear is completed
when the clearing
display disappears.