8 Communications Functions
8 - 92
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
Recalculates internal parameters.
The recalculation is required if the base frequency or motor parameters (H***) are changed via RS485
communications.
Transmission Frame
Response frame
Positive response: Refer to page 8-92
Negative response: Refer to page 8-93
<Positive Response>
Response frame
Command 0B
Frame format
STX Station
No.
Command BCC CR
Description Data size Setting
STX Control code (Start of Text) 1 byte STX (0x02)
Station
No.
Station No. of target Inverter 2 bytes 01 to 32
Command
Transmission command 2 bytes 0B
BCC Block check code 2 bytes
Exclusive OR of frame segments from
Station No. to Data (Refer to page 8-94.)
CR Control code (Carriage Return) 1 byte CR (0x0D)
Positive and Negative Responses
Frame format
STX Station
No.
ACK BCC CR
Description Data size Setting
STX Control code (Start of Text) 1 byte STX (0x02)
Station
No.
Station No. of target Inverter 2 bytes 01 to 32
ACK Control code (ACKnowledge) 1 byte ACK (0x06)
BCC Block check code 2 bytes
Exclusive OR of frame segments from
Station No. to Data (Refer to page 8-94.)
CR Control code (Carriage Return) 1 byte CR (0x0D)