5 Basic Settings
5 - 46
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
Enable/disable the STOP/RESET key on the Digital Operator or LCD Digital Operator.
This setting is enabled when the RUN Command Selection (A002) is not set to 02 (Digital Operator).
However, when the RUN Command Selection (A002) is set to 02 (Digital Operator), the
STOP/RESET key is enabled independent of this setting.
Precautions for Safe Use
The STOP/RESET key on the Digital Operator or LCD Digital Operator is enabled only when the
STOP Key Selection parameter is set to Enabled.
Be sure to provide a separate emergency stop switch.
5-7-3 STOP Key Selection
Parameter
No.
Function name Data
Default
data
Unit
b087 STOP Key Selection
00: Enabled
01: Disabled
02: Only STOP function disabled
00
Data
STOP command via STOP/
RESET key on Digital Operator
Trip reset via STOP/RESET key
on Digital Operator
00 Enabled Enabled
01 Disabled Disabled
02 Disabled Enabled