7 Detailed Functions
7 - 88
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
If the inverter detects a power supply shutoff during operation, this function causes the motor to stop
after deceleration so that the internal DC voltage of the inverter is maintained at the Deceleration
Hold Level on Power Interruption (b052).
This function can be enabled in three ways in the Deceleration Stop Selection on Power Interruption
(b050).
This function does not reset until the motor stops running. To restart the inverter after power recovery
with this function activated, turn ON the STOP command input (to turn OFF the RUN command OFF)
and then turn ON the RUN command input again.
Function options for Multi-function Input S1 to S8 Selection (C001 to C008)
44: BOK Brake confirmation
45: ORT Orientation
47: PCLR Position deviation clear
48: STAT Pulse train position command permission
52: ATR Torque command input permission
54: SON Servo ON
55: FOC Preliminary excitation
66: CP1 Position command selection 1
67: CP2 Position command selection 2
68: CP3 Position command selection 3
69: ORL Zero return limit signal
70: ORG Zero return startup signal
71: FOT Forward driving stop
72: ROT Reverse driving stop
73: SPD Speed/Position switching
Function options for Multi-function Output P1 to P5 Selection/Multi-function Relay Output (MA, MB)
Function Selection (C021 to C026)
19: BRK Brake release
20: BER Brake error
22: DSE Excessive speed deviation
23: POK Position ready
Deceleration Stop on Power Interruption Function
Parameter
No.
Function name Data Default data Unit
b050
Deceleration Stop Selection
on Power Interruption
00: Disabled
01: Enabled (deceleration stop)
02: Enabled (Constant voltage, without
recovery)
03: Enabled (Constant voltage, with
recovery)
00
b051
Starting Voltage on Power
Interruption
0.0 to 999.9
1000.
220/440 V
b052
Deceleration Hold Level on
Power Interruption
0.0 to 999.9
1000.
360/720 V