EasyManua.ls Logo

Omron RX Series - RUN Command Settings; RUN Command Selection

Omron RX Series
688 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5 - 23
5 Basic Settings
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
5-4 RUN Command Settings
5
5-4-1 RUN Command Selection
5-4 RUN Command Settings
Select the input method for the RUN command.
Below are the details of the parameter settings.
5-4-1 RUN Command Selection
Parameter
No.
Function name Data Default data Unit
A002
RUN Command
Selection
01: Control circuit terminal block
02: Digital Operator (F001)
03: Modbus communication
04: Option 1
05: Option 2
02
Related functions F004, C001 to C008, C019
Data RUN command source
01
Inputs the RUN command via the ON/OFF of the FW/RV signal allocated to the control circuit
terminal block.
It will be regarded as the STOP command if both the forward and reverse commands are input
simultaneously.
02
Inputs the RUN command via the RUN key and the STOP/RESET key on the Digital Operator or
LCD Digital Operator.
03 Inputs the RUN command via Modbus communication.
04 Inputs the RUN command via the option board mounted on the option port 1.
05 Inputs the RUN command via the option board mounted on the option port 2.

Table of Contents

Related product manuals