• Use this function to adjust the inverter output voltage as 100% of the voltage set in the Motor Rated
Voltage Selection (A082).
• You can avoid motor hunting by decreasing the value set in the Output Voltage Gain.
• Use this function to apply DC injection braking to the motor according to the load.
• Two types of DC injection braking are available: via a multifunction input terminal that is allocated to
07: DB (External DC injection braking), and automatic application at the time when the motor is
started or stopped.
Note, however that the use of DC injection braking may not be able to stop the motor due to the
moment of inertia of the motor load.
Output Voltage Gain
Parameter No. Function name Data
Default data
Unit
A045 Output Voltage Gain 20. to 100. 100. %
Related functions A082
DC Injection Braking
Parameter No. Function name Data
Default data
Unit
A051
DC Injection
Braking Selection
00: Disabled
01: Enabled
02: Enabled (Operates only at set frequency)
00 –
A052
DC Injection
Braking Frequency
0.00 to 99.99
100.0 to 400.0
0.50 Hz
A053
DC Injection
Braking Delay Time
0.0 to 5.0 0.0 s
A054
DC Injection
Braking Power
Heavy load (CT)
0. to 100. (0.4 to 55 kW)
50
%
0. to 80. (75 to 132 kW)
40
Light load (VT)
0. to 70. (0.4 to 55 kW)
50
0. to 50. (75 to 132 kW)
40
A055
DC Injection
Braking Time
0.0 to 60.0 0.5 s
A056
DC Injection
Braking Edge/Level
Selection
00: Edge operation
01: Level operation
01 –
A057
Startup DC
Injection Braking
Power
Heavy load (CT)
0. to 100. (0.4 to 55 kW)
0.
%
0. to 80. (75 to 132 kW)
0.
Light load (VT)
0. to 70. (0.4 to 55 kW)
0.
0. to 50. (75 to 132 kW)
0.
A058
Startup DC Injection
Braking Time
0.0 to 60.0 0.0 s
A045