6 Vector Control
6 - 4
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
6-2 Sensorless Vector Control
Set the 1st/2nd Control Method (A044/A244) to 03 (Sensorless vector control).
Set the 1st/2nd Motor Capacity (H003/H203) and the 1st Motor Pole Number (H004/H204) according
to your motor.
In the 1st/2nd Base Frequency (A003/A203), set the rated frequency of the motor. In the Motor Rated
Voltage Selection (A082), set the rated voltage of the motor.
To use this function, be sure to set the motor parameters appropriately according to
6-2-3 Auto-tuning
of Motor Parameters on page 6-5.
Set the 1st/2nd Control Method (A044/A244) to 04 (0-Hz sensorless vector control).
Set the 1st/2nd Motor Capacity (H003/H203) and the 1st Motor Pole Number (H004/H204) according
to your motor.
In the 1st/2nd Base Frequency (A003/A203), set the rated frequency of the motor. In the Motor Rated
Voltage Selection (A082), set the rated voltage of the motor.
To use this function, be sure to set the motor parameters appropriately according to 6-3-4 Auto-tuning
of Motor Parameters on page 6-18.
Use the 1st/2nd Limit at 0 Hz (H060/H260) to set the current under constant current control in a 0-Hz
range (approximately 3.0 Hz or less). Set this as a percentage of the rated current of the inverter.
In the 1st Boost Amount at SLV Startup, 0 Hz (H061/H261), set the amount of current boost during
startup. Set this as a percentage of the rated current of the inverter. The value set here will be added
to the value set in the 1st Limit at 0 Hz (H060/H260) during startup only.
0-Hz sensorless vector control cannot be used in the light load mode. Be sure to set the Heavy
Load/Light Load Selection (b049) to 00 (Heavy load mode).
6-2-1 Sensorless Vector Control Parameter Settings
Parameter
No.
Function name Data Default data Unit
A044/A244
1st/2nd Control Method
*1
*1. To enable the switching to the 2nd control, allocate one of the Multi-function Input S1 to S8 Selection (C001 to
C008) to 08 (SET) and turn ON that terminal.
03: Sensorless vector control
*2
*2. Sensorless vector control can be selected for the 1st/2nd control only.
00
H003/H203 1st/2nd Motor Capacity
0.2/0.4/0.55/0.75/1.1/1.5/2.2/3.0/3.7/4.0/
5.5/7.5/11.0/15.0/18.5/22/30/37/45/55/
75/90/110/132
Maximum
applicable
motor capacity
kW
H004/H204
1st/2nd Motor Pole
Number
2/4/6/8/10 4 pole
A003/A203 1st/2nd Base Frequency
30. to 1st/2nd Maximum Frequency
(A004/A204)
60 Hz
A082
Motor Rated Voltage
Selection
200-V class: 200 V/215 V/220 V/230 V/
240 V
200 V
400-V class: 380 V/400 V/415 V/440 V/
460 V/480 V
400 V
6-2-2 0-Hz Sensorless Vector Control Parameter Settings