6 Vector Control
6 - 48
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
In the Origin Search Mode (P068), select one of the three origin search modes. When origin search is
completed, a new origin is established with the Current Position Monitor (d030) cleared (= 0).
Allocate one of the Multi-function Input S1 to S8 Selection (C001 to C008) to 54 (SON: Servo ON) and
turn ON that terminal SON. Then, start the origin search operation.
Set the origin search direction in the Origin Search Direction Selection (P069).
Unless you perform origin search operation, the position in which the power supply is turned ON will be
used as the origin for position control.
*1 The reset function does not initialize the internal data including position control settings.
*2 The default data was changed from the previous model.
6-7-3 Origin Search Function
Parameter No. Function name Data Default data Unit
P068 Origin Search Mode
00: Origin search mode 1
01: Origin search mode 2
02: Origin search mode 3
00 –
P069
Origin Search Direction
Selection
00: Forward side
01: Reverse side
00 –
P070
Origin Search Mode 1
Frequency
0.00 to 10.00
5.00
*2
Hz
P071
Origin Search Mode 2
Frequency
0.00 to 1st Maximum Frequency (A004)
5.00
*2
Hz
C001 to C008
Multi-function Input S1 to
S8 Selection
69: ORL (Zero return limit signal)
70: ORG (Zero return startup signal)
––
C102 Reset Selection
03: Trip reset only
*1
02 –
d030 Current Position Monitor
–268435455 to 268435455
(P012 = 02)
–1073741823 to 1073741823
(P012 = 03)
Displays MSB 4digits (1digit for “–”)
––