12 - 61
12 Options
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
12-15 CompoNet Communications Unit
(Model: 3G3AX-RX-CRT-E)
12
12-15-1 Specifications
12-15
CompoNet Communications Unit
(Model: 3G3AX-RX-CRT-E)
12-15-1 Specifications
Item Specifications
Mounting
Unit type RX Series CompoNet Communications Unit
Model 3G3AX-RX-CRT-E
Dimensions
[Width x Height x Depth]
80 × 67 × 49 mm
Weight Approx. 170 g
Environment
Operating ambient
temperature
–10 to 50°C (with no freezing or condensation)
Operating ambient humidity 20% to 90%
Storage ambient temperature –20 to 65°C (with no freezing or condensation)
Vibration resistance
5.9 m/s
2
(0.6 G), 10 to 55 Hz
Dielectric strength 500 VAC (between isolated circuits)
Location At a maximum altitude of 1,000 m (without corrosive gases or dust)
Conformance to EMC and
electrical safety standards
EN61800-3: 2004 (2004/108/EC) Second environment, Category C3
EN61800-5-1: 2007 (2006/95/EC) SELV
Internal power supply Supplied from Inverter
Enclosure rating IP20
DeviceNet
interface
Communications protocol CompoNet
Certification CompoNet conformance test
CompoNet profile AC drive (0x02)
Supported connections
Remote I/O: Master-Slave connection
Poll
Explicit message
Conforming to the CompoNet specifications
Communications power
supply
– (External power supply not required)
Unit device address range
Node address MAC ID 0 to 63, set via Inverter parameter P190 or rotary
switch
Supported baud rates
4 Mbps, 3 Mbps, 1.5 Mbps, or 93.75 kbps
Automatic baud rate detection by Master Unit
DeviceNet
configuration
Default connection path Supported, set via Inverter parameter P046
Supported assemblies
Basic Speed I/O (Output assembly 20, Input assembly 70)
Extended Speed I/O (21, 71)
Extended Speed and Torque Control (123, 173)
Special I/O (100, 150)
Extended Control I/O (101, 151)
Extended Control I/O and Multi-function Input Monitor (101, 153)
Flexible Format (139, 159)
Extended Speed and Acceleration Control (110, 111)
*1
*1. Use the specified output and input assembly pair.
EDS file Dependent on Inverter model