4 - 39
4 Parameter List
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
4-3 Extended Function Mode
4
4-3-4 Group H: Motor Control Parameters
4-3-4 Group H: Motor Control Parameters
Parameter
No.
Function name Monitor or data range
Default
data
Changes during
operation
Unit Page
Normal
b031 = 10
H001 Auto-tuning
Selection
00: Disabled
01: Enabled (No motor rotation)
02: Enabled (Motor rotation)
00 Disabled Disabled – 6-5
H002 1st Motor
Parameter
selection
00: Standard motor parameter
01: Auto-tuning
02: Auto-tuning (Online
auto-tuning enabled)
00 Disabled Disabled –
H202 2nd Motor
Parameter
selection
00: Standard motor parameter
01: Auto-tuning
02: Auto-tuning (Online
auto-tuning enabled)
00 Disabled Disabled –
H003 1st Motor
Capacity
0.1/0.2/0.4/0.55/0.75/1.1/
1.5/2.2/3.0/3.7/4.0/5.5/7.5/
11.0/15.0/18.5/22/30/37/45/55/75/
90/110/132
Maximum
applicable
motor
capacity
Disabled Disabled kW
H203 2nd Motor
Capacity
Disabled Disabled
H004 1st Motor Pole
Number
2/4/6/8/10 4 Disabled Disabled pole
H204 2nd Motor Pole
Number
4 Disabled Disabled
H005 1st Speed
Response
0.001 to 9.999
10.00 to 80.00
(10.000 to 80.000)
1.590 Enabled Enabled – 6-27
H205 2nd Speed
Response
1.590
H006 1st Stabilization
Parameter
0. to 255. 100. Enabled Enabled – 7-146
H206 2nd Stabilization
Parameter
100.
H306 3rd Stabilization
Parameter
100.
H020 1st Motor
Parameter R1
0.001 to 9.999
10.00 to 65.53
Depends on
the motor
capacity.
Disabled Disabled Ω 6-11
H220 2nd Motor
Parameter R1
Depends on
the motor
capacity.
H021 1st Motor
Parameter R2
0.001 to 9.999
10.00 to 65.53
Depends on
the motor
capacity.
Disabled Disabled Ω
H221 2nd Motor
Parameter R2
Depends on
the motor
capacity.
H022 1st Motor
Parameter L
0.01 to 99.99
100.0 to 655.3
Depends on
the motor
capacity.
Disabled Disabled mH
H222 2nd Motor
Parameter L
Depends on
the motor
capacity.
H023 1st Motor
Parameter Io
0.01 to 99.99
100.0 to 655.3
Depends on
the motor
capacity.
Disabled Disabled A
H223 2nd Motor
Parameter Io
Depends on
the motor
capacity.