4 Parameter List
4 - 40
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
H024 1st Motor
Parameter J
0.001 to 9.999
10.00 to 99.99
100.0 to 999.9
1000. to 9999.
Depends on
the motor
capacity.
Disabled Disabled
kg/m
2
6-11
H224 2nd Motor
Parameter J
Depends on
the motor
capacity.
H030 1st Motor
Parameter R1
(Auto-tuning Data)
0.001 to 9.999
10.00 to 65.53
Depends on
the motor
capacity.
Disabled Disabled Ω 6-5
H230 2nd Motor
Parameter R1
(Auto-tuning Data)
Depends on
the motor
capacity.
H031 1st Motor
Parameter R2
(Auto-tuning Data)
0.001 to 9.999
10.00 to 65.53
Depends on
the motor
capacity.
Disabled Disabled Ω
H231 2nd Motor
Parameter R2
(Auto-tuning Data)
Depends on
the motor
capacity.
H032 1st Motor
Parameter L
(Auto-tuning Data)
0.01 to 99.99
100.0 to 655.3
Depends on
the motor
capacity.
Disabled Disabled mH
H232 2nd Motor
Parameter L
(Auto-tuning Data)
Depends on
the motor
capacity.
H033 1st Motor
Parameter Io
(Auto-tuning Data)
0.01 to 99.99
100.0 to 655.3
Depends on
the motor
capacity.
Disabled Disabled A
H233 2nd Motor
Parameter Io
(Auto-tuning Data)
Depends on
the motor
capacity.
H034 1st Motor
Parameter J
(Auto-tuning Data)
0.001 to 9.999
10.00 to 99.99
100.0 to 999.9
1000. to 9999.
Depends on
the motor
capacity.
Disabled Disabled
kg/m
2
H234 2nd Motor
Parameter J
(Auto-tuning Data)
Depends on
the motor
capacity.
H050
1st PI Proportional
Gain
0.0 to 999.9
1000.
100.0 Enabled Enabled 6-27
H250
2nd PI Proportional
Gain
100.0
H051
1st PI Integral Gain
0.0 to 999.9
1000.
100.0 Enabled Enabled 6-28
H251
2nd PI Integral
Gain
100.0
H052 1st P Proportional
Gain
0.01 to 10.00 1.00 Enabled Enabled
H252 2nd P
Proportional Gain
1.00
H060 1st Limit at 0 Hz 0.0 to 100.0 100.0 Enabled Enabled % 6-4
H260 2nd Limit at 0 Hz 100.0
Parameter
No.
Function name Monitor or data range
Default
data
Changes during
operation
Unit Page
Normal
b031 = 10
Control parameters

Table of Contents