4 - 41
4 Parameter List
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
4-3 Extended Function Mode
4
4-3-4 Group H: Motor Control Parameters
Parameter
No.
Function name Monitor or data range
Default
data
Changes during
operation
Unit Page
Normal
b031 = 10
H061
1st Boost Amount
at SLV Startup, 0 Hz
0. to 50. 50. Enabled Enabled % 6-4
H261
2nd Boost Amount
at SLV Startup, 0 Hz
50.
H070 For PI
Proportional Gain
Switching
0.0 to 999.9
1000.
100.0 Enabled Enabled – 6-29
H071 For PI Integral
Gain Switching
0.0 to 999.9
1000.
100.0 Enabled Enabled –
H072 For P Proportional
Gain Switching
0.00 to 10.00 1.00 Enabled Enabled –
H073 Gain Switching
Time
0. to 9999. 100. Enabled Enabled ms