5 Basic Settings
5 - 24
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
5-5 Frequency Reference Settings
• Select the input method for the frequency reference.
• When the multi-step speed reference function is used (by setting the multi-function input terminals for
the Multi-step Speed Reference 0 to 15), the value set in A001 is effective only for the Frequency
Reference 0.
The values set in the Frequency Reference 1 to 15 have priority over the value set in A001.
*1 This setting is enabled when the 3G3AX-OP01 is connected.
Below are the details of the parameter data.
*1 Refer to 6-2 Sensorless Vector Control on page 6-4 .
*2 Refer to “DriveProgramming User’s Manual (I580)”.
*3 Refer to Calculation Frequency Function on page 7-59.
5-5-1 Frequency Reference Selection
Parameter
No.
Function name Data Default data Unit
A001
Frequency
Reference
Selection
00: Digital Operator (Volume adjuster) *1
01: Control circuit terminal block (Analog
input)
02: Digital Operator (F001)
03: Modbus communication
04: Option 1
05: Option 2
06: Pulse train frequency
07: DriveProgramming
10: Operation function output
02 –
Related functions A005, A141 to A143, A145, A146
Data Frequency reference source
00
Sets the frequency reference via the volume adjuster on the external Digital Operator
(3G3AX-OP01).
01
Sets the frequency reference via the control circuit terminal block (analog input signals). (FV-FC,
FI-FC, FE-FC)
02
Sets the frequency reference via the Digital Operator or LCD Digital Operator. (Output
Frequency Setting: F001)
03 Sets the frequency reference via Modbus communication.
04 Sets the frequency reference via the option board mounted on the option port 1.
05 Sets the frequency reference via the option board mounted on the option port 2.
06
Sets the frequency reference as a pulse train via the 3G3AX-PG01.
*1
07
Sets the frequency reference via the DriveProgramming.
*2
10
Sets the calculation result of the frequency operation function as the frequency reference.
*3