5 - 25
5 Basic Settings
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
5-5 Frequency Reference Settings
5
5-5-1 Frequency Reference Selection
Precautions for Correct UsePrecautions for Correct Use
The Output Frequency Setting/Monitor (F001) shows the frequency reference configured in the
internal memory (RAM).
F001 displays the frequency reference value selected at that time.
If you change the frequency reference value displayed in F001 and save it (by pressing the Enter
key), the data will be stored with the frequency reference selected at that time.
For the frequency reference 0, the data will be stored with the 1st Multi-step Speed Reference
0 (A020)/2nd Multi-step Speed Reference 0 (A220)/3rd Multi-step Speed Reference 0 (A320)
according to the 1st/2nd/3rd Control Method selection.
For the multi-step speed reference 1 to 15, the data will be stored with the corresponding
Multi-step Speed Reference 1 to 15 (A021 to A035).
* The frequency reference selection of Digital Operator (Volume adjuster), Control terminal block
(Analog input), Modbus communication, Options, DriveProgramming, and Operation function
output cannot be changed in F001.