Even if the Free V/f Voltage 1 to 7 are set to 800 V, the inverter cannot produce output voltage
higher than the input voltage or the value of the Motor Rated Voltage Selection (A082).
Be sure to check that the output characteristic setting is proper. An improper setting causes
overcurrent during acceleration or deceleration, or vibration of the motor and/or machine.
b101 Free V/f Voltage 1 (V1)
0.0 to 800.0
Set the voltage
at each break
point.
0.0 V
b103 Free V/f Voltage 2 (V2)
b105 Free V/f Voltage 3 (V3)
b107 Free V/f Voltage 4 (V4)
b109 Free V/f Voltage 5 (V5)
b111 Free V/f Voltage 6 (V6)
b113 Free V/f Voltage 7 (V7)
Related functions A044, A244, A344
Parameter No. Function name Data Description Default data Unit
(Example)
Output voltage [V]
V7
V6
V5
V4
V1
V2,V3
f1
0
f2 f3 f4 f5 f6 f7
Output frequency [Hz]
Output
voltage [V]
V7
V6
0
f6
f7 Output frequency [Hz]
Select the voltage or motor
voltage applicable for output.
The output voltage will be limited to the
applicable voltage even if exceeded.