7 - 95
7 Detailed Functions
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
7-4 Detailed Functions (Group b)
7
The parameter initialization function restores the changed parameters to the factory default settings.
It also can clear the fault monitor data.
As a measure to prevent inadvertent parameter initialization, the inverter is designed to force the user
to set several parameters to execute initialization.
The following parameters are not initialized: the settings of the DriveProgramming User Parameters
U00 to U31 (P100 to P131), Total RUN Time Monitor (d016), Total Power ON Time Monitor (d017),
Initialization Data Selection (b085), Heavy Load/Light Load Selection (b049), Thermistor Adjustment
(C085), and analog adjustment parameters (C081 to C083, C121 to C123).
If you use the 3G3RX-V1 Series Inverter for the first time or newly configure settings, execute 04
(Clear fault monitor + initialize data + Clear DriveProgramming) in b084.
Remember that you cannot restore the initialized data to the previous settings once you execute
parameter initialization.
Precautions for Correct UsePrecautions for Correct Use
The 3G3RX-V1 Series Inverter does not support the conventional initialization which is
performed by pressing multiple keys simultaneously.
Parameter Initialization
Parameter No. Function name Data
Default
data
Unit
b084
Initialization
Selection
00: Initialization disabled
01: Clear fault monitor
02: Initialize data
03: Clear fault monitor + initialize data
04: Clear fault monitor + initialize data +
Clear DriveProgramming
00
b085
Initialization Data
Selection
00: Do not change.
00
b180
Initialization
Execution
*1
*1.Remember that it is impossible to undo the initialization once you press the Enter key ( ) to execute
parameter initialization, with the Initialization Execution (b180) set to 01.
00: Function disabled
01: Execute initialization
00