7 - 97
7 Detailed Functions
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
7-4 Detailed Functions (Group b)
7
Enable/disable the STOP/RESET key on the Digital Operator or LCD Digital Operator.
This setting is enabled when the RUN Command Selection (A002) is not set to 02 (Digital Operator).
However, when the RUN Command Selection (A002) is set to 02 (Digital Operator), the STOP/RESET
key is enabled independent of this setting.
Precautions for Safe Use
The STOP/RESET key on the Digital Operator or LCD Digital Operator is enabled only when
the STOP Key Selection parameter is set to Enabled. Be sure to provide a separate
emergency stop switch.
Select whether the motor is stopped by a deceleration stop according to the deceleration time setting
or a free-run stop, when the STOP command is input via the Digital Operator or the control circuit
terminal block.
If the RUN command is input again during free run, the inverter will restart according to the Free-run
Stop Selection (b088) setting. (Refer to Free-run Stop Selection on page 7-98.)
STOP Key Selection
Parameter No. Function name Data Default data Unit
b087 STOP Key Selection
00: Enabled
01: Disabled
02: Only resetting enabled
00
Data
STOP command via STOP/RESET
key on Digital Operator
Trip reset operation via
STOP/RESET key on Digital
Operator
00 Enabled Enabled
01 Disabled Disabled
02 Disabled Enabled
Stop Selection
Parameter No. Function name Data Default data Unit
b091 Stop Selection
00: Deceleration stop
01: Free-run stop
00