6 Vector Control
6 - 6
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
Offline auto-tuning consists of the following five steps:
• Presetting of parameters
• Selection of motor rotation during auto-tuning
• Auto-tuning
• Operations after auto-tuning
• Operations in case of error
1
Presetting of parameters
(1) Set the 1st Motor Capacity (H003) and the 1st Motor Pole Number (H004) according to
your motor.
(2) Set the 1st Base Frequency (A003) to the rated frequency of the motor and the Motor
Rated Voltage Selection (A082) to the rated voltage of the motor.
(3) Change the DC Injection Braking Selection (A051) from 01 (Enabled) to 00 (Disabled).
If the DC Injection Braking Selection (A051) is set to 01 (Enabled), change it to 00
(Disabled). If it is set to enabled, auto-tuning will not complete.
(4) Set the Output Voltage Gain (A045) to 100%.
This parameter is set to 100% by default. Restore it to 100% if the data is different.
(5) Make sure that the torque reference input permission terminal (52: ATR) is OFF.
Correct measurement is not possible when the terminal is ON.
H030/H230
1st/2nd Motor Parameter
R1 (Auto-tuning Data)
0.001 to 9.999
10.00 to 65.53
Dependent on
motor capacity
O
H031/H231
1st/2nd Motor Parameter
R2 (Auto-tuning Data)
H032/H232
1st/2nd Motor Parameter
L (Auto-tuning Data)
0.01 to 99.99
100.0 to 655.3
mH
H033/H233
1st/2nd Motor Parameter
lo (Auto-tuning Data)
A
H034/H234
1st/2nd Motor Parameter J
(Auto-tuning Data)
0.001 to 9.999
10.00 to 99.99
100.0 to 999.9
1000. to 9999.
kg/m
2
A003/A203 1st/2nd Base Frequency
30. to 1st/2nd Maximum Frequency
(A004/A204)
60 Hz
A051
DC Injection Braking
Selection
00: Disabled
01: Enabled
02: Enabled (Operates only at set
frequency)
00 –
A082
Motor Rated Voltage
Selection
200-V class: 200/215/220/230/240 200
V
400-V class: 380/400/415/440/460/480 400
Offline Auto-Tuning Steps
Parameter
No.
Function name Data Default data Unit