4 Parameter List
4 - 8
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
Parameter
No.
Function name Monitor or data range
Default
data
Changes during
operation
Unit Page
Normal
b031 = 10
A005 FV/FI Selection 00: Switching between FV
(Voltage) and FI (Current) via
terminal AT
02: Switching between FV and
volume adjuster via terminal AT
03: Switching between FI and
volume adjuster via terminal AT
04: Switching between FE and
volume adjuster via terminal AT
00 Disabled Disabled – 7-21
A006 FE Selection 00: FE only
01: FV/FI auxiliary frequency
reference (not reversible)
02: FV/FI auxiliary frequency
reference (reversible)
03: FE disabled
03 Disabled Disabled –
A011 FV Start
Frequency
*1
0.00 to 99.99
100.0 to 400.0
0.00 Disabled Enabled Hz 7-24
A012 FV End
Frequency
*1
0.00 to 99.99
100.0 to 400.0
0.00 Disabled Enabled Hz
A013 FV Start Ratio 0. to FV End Ratio (A014) 0. Disabled Enabled %
A014 FV End Ratio FV Start Ratio (A013) to 100. 100. Disabled Enabled %
A015 FV Start Selection 00: FV Start Frequency (A011)
01: 0 Hz
01 Disabled Enabled –
A016 Analog Input Filter 1. to 30. (x 2 ms)
31. : With 500 ms filter ±0.1 Hz
hysteresis
31. Disabled Enabled – 7-26
A017
DriveProgramming
Function Selection
00: Disabled
01: Enabled (Start/stop via
multi-function input PRG
terminal)
02: Enabled (Start/stop via power
on/off)
00 Disabled Disabled – 7-26
*1 The inverter operates at 0 to 9.8 V when A011and A012 are set to 0.00.