5 - 11
5 Basic Settings
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
5-2 V/f Control Settings
5
5-2-1 Control Method (V/f Characteristics)
Precautions for Correct UsePrecautions for Correct Use
Even if the Free V/f Voltage 1 to 7 are set to 800 V, the inverter cannot produce output voltage
higher than the input voltage or the value of the Motor Rated Voltage Selection (A082).
Be sure to check that the output characteristic setting is proper. An improper setting causes
overcurrent during acceleration or deceleration, or vibration of the motor and/or machine.
b101 Free V/f Voltage 1 (V1)
0. to 800.0
Set the voltage at
each break point.
0.0 V
b103 Free V/f Voltage 2 (V2)
b105 Free V/f Voltage 3 (V3)
b107 Free V/f Voltage 4 (V4)
b109 Free V/f Voltage 5 (V5)
b111 Free V/f Voltage 6 (V6)
b113 Free V/f Voltage 7 (V7)
Related functions A044, A244, A344
Parameter
No.
Function name Data Description
Default
data
Unit
(Example) Output voltage [V]
V7
V6
V5
V4
V1
V2, V3
f10
f2 f3 f4 f5 f6 f7
Output frequency [Hz]
V7
V6
0f6
f7 Output frequency [Hz]
The output voltage will be limited to
the applicable voltage even if
exceeded.
Output voltage [V]