5 Basic Settings
5 - 14
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
b022
Overload
Limit Level
0.20 x Heavy-load rated
current to 2.00 x Heavy-load
rated current [A] (0.20 x
Heavy-load rated current to
1.80 x Heavy-load rated
current [A]
0.20 x Light-load rated
current to 1.50 x Light-load
rated current [A] (0.20 x
Light-load rated current to
1.50 x Light-load rated
current [A])
1.50 x
Heavy-load
rated
current [A]
1.20 x
Light-load
rated
current [A]
Enabled
Conversion
*1
b025
Overload
Limit Level 2
b028
Frequency
Pull-in
Restart Level
0.20 x Heavy-load rated
current to 2.00 x Heavy-load
rated current [A] (0.20 x
Heavy-load rated current to
1.80 x Heavy-load rated
current [A])
0.20 x Light-load rated
current to 1.50 x Light-load
rated current [A] (0.20 x
Light-load rated current to
1.50 x Light-load rated
current [A])
Heavy-load
rated
current [A]
Light-load
rated
current [A]
Enabled
Conversion
*1
b041
Torque Limit 1
(Four-quadrant
Mode Forward
Power
Running)
Percentage of heavy-load
rated current
0. to 200.[%] (0. to 180.[%])
no: Function disabled
Percentage of light-load
rated current
0. to 150.[%] (0. to 150.[%])
no: Function disabled
150.[%] 120.[%] Enabled Disabled
b042
Torque Limit 2
(Four-quadrant
Mode Reverse
Regeneration)
b043
Torque Limit 3
(Four-quadrant
Mode Reverse
Power
Running)
b044
Torque Limit 4
(Four-quadrant
Mode Forward
Regeneration)
b083
Carrier
Frequency
0.5 to 15.0 [kHz] (0.5 to 10.0
[kHz])
0.5 to 12.0 [kHz] (0.5 to 8.0
[kHz])
5.0 [kHz]
(3.0 [kHz])
3.0 [kHz]
(3.0 [kHz])
Enabled Disabled
C030
Digital
Current
Monitor
Reference
Value
0.20 x Heavy-load rated
current to 2.00 x Heavy-load
rated current [A]
0.20 x Light-load rated
current to 1.50 x Light-load
rated current [A]
Heavy-load
rated
current [A]
Light-load
rated
current [A]
Enabled
Conversion
*1
C039
Low Current
Detection
Level
0.00 x Heavy-load rated
current to 2.00 x Heavy-load
rated current [A] (0.00 x
Heavy-load rated current to
1.80 x Heavy-load rated
current [A])
0.00 x Light-load rated
current to 1.50 x Light-load
rated current [A] (0.00 x
Light-load rated current to
1.50 x Light-load rated
current [A])
Heavy-load
rated
current [A]
Light-load
rated
current [A]
Enabled
Conversion
*1
C041
Overload
Warning
Level
0.00 x Heavy-load rated
current to 2.00 x Heavy-load
rated current [A] (0.00 x
Heavy-load rated current to
1.80 x Heavy-load rated
current [A])
0.00: Function disabled
0.00 x Light-load rated
current to 1.50 x Light-load
rated current [A] (0.00 x
Light-load rated current to
1.50 x Light-load rated
current [A])
0.00: Function disabled
Heavy-load
rated
current [A]
Light-load
rated
current [A]
Enabled
Conversion
*1
No.
Parameter
name
Setting range Default data
Initialization at
mode switching
Heavy load (CT) Light load (VT)
Heavy load
(CT)
Light load
(VT)
Heavy
to Light
Light to
Heavy