5 Basic Settings
5 - 28
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
To switch between analog voltage and analog current inputs to set the frequency reference, set the
parameters as follows.
This enables switching between the frequency reference input (voltage reference) and frequency
reference input (current reference) terminals.
To switch between these analog input signals, use the terminal AT (Analog input switching) allocated to
a multi-function input terminal.
Frequency reference input (Voltage reference), between terminal FV and FC: 0 to 9.8 VDC
Frequency reference input (Current reference), between terminal FI and FC: 4 to 19.8 mA
Note By default, each analog input signal is set to reach the maximum frequency at 9.8 V or 19.8 mA.
*1 When the terminal AT is ON, the frequency reference input (current reference) terminal is enabled.
Using an Analog Voltage Input or Analog Current Input by Switching
Parameter No. Function name Data
Default
data
Unit
A001
Frequency
Reference Selection
01: Control circuit terminal block
(Analog input)
02
A005
FV/FI Selection
*1
00: Switching between FV and FI via
terminal AT
00
A006 FE Selection 03: FE disabled 03
C001 to C008
Multi-function Input
S1 to S8 Selection
16: Terminal AT (Analog input
switching)
––
V
A