5 Basic Settings
5 - 34
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
When an input is made to FE with the lower limit set, the rotation frequency at 0 V is fixed to the
forward-side lower limit (A062/A262) or the reverse-side lower limit setting (A062/A262), as shown
below.
The graph below shows the FE characteristics with the default analog adjustment function settings (FE:
A111 to A114).
RUN Command Selection (A002) = 01 (Control circuit terminal block)
RUN Command Selection (A002) = 02 (Digital Operator)
When Using FE-FC
Terminal Rotation when FE = 0 V
FW (ON) A062 (Forward side)
RV (ON) A062 (Reverse side)
RUN Direction Selection (F004) Rotation when FE = 0 V
00: Forward A062 (Forward side)
01: Reverse A062 (Reverse side)
Maximum
frequency
A004/A204
A061
A062
10 V
–10 V
A062
A061
Maximum
frequency
A004/A204
ForwardReverse