• If the reset signal is input during the restart standby time, the frequency at shutoff value stored
in the inverter will be cleared, resulting in a 0-Hz start.
• The details of the Starting Frequency Selection at Frequency Pull-in Restart (b030) are shown
below.
Set value Description Explanation
00
Frequency at
shutoff
Executes pull-in restart at frequency at which inverter
output is shut off.
01
Maximum
frequency
Executes pull-in restart at maximum frequency.
02 Set frequency
Executes pull-in restart at reference frequency at which
inverter operates normally.