EasyManua.ls Logo

Omron RX Series - Page 251

Omron RX Series
688 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5 - 55
5 Basic Settings
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
5-9 Multi-function Input Settings
5
5-9-5 Multi-step Speed Operation Function
Setting the Multi-function Input S1 to S8 Selection (C001 to C008) to 32 (SF1) to 38 (SF7) enables
the selection of the 0th to 7th multi-step speed.
Use the Multi-step Speed Reference 1 to 7 (A021 to A027) to set the frequency for SF1 to SF7.
For the Multi-step Speed Reference 0, set the Frequency Reference Selection (A001).
To enable the 1st/2nd/3rd frequency reference 0 setting, set A001 to 02 (Digital Operator: F001).
If this parameter is set to 01 (Control circuit terminal block: Analog input), the frequency reference for
the Multi-step Speed Reference 0 is set via analog input.
Bit Operation
Parameter
No.
Function name Data Default data Unit
C001 to
C008
Multi-function Input S1 to S8
Selection
32: SF1 (Multi-step speed setting
bit 1)
––
33: SF2 (Multi-step speed setting
bit 2)
––
34: SF3 (Multi-step speed setting
bit 3)
––
35: SF4 (Multi-step speed setting
bit 4)
––
36: SF5 (Multi-step speed setting
bit 5)
––
37: SF6 (Multi-step speed setting
bit 6)
––
38: SF7 (Multi-step speed setting
bit 7)
––
Multi-step
speed
SF7 SF6 SF5 SF4 SF3 SF2 SF1
0th OFF OFF OFF OFF OFF OFF OFF
1st
Disabled Disabled Disabled Disabled Disabled Disabled
ON
2nd
Disabled Disabled Disabled Disabled Disabled
ON OFF
3rd
Disabled Disabled Disabled Disabled
ON OFF OFF
4th
Disabled Disabled Disabled
ON OFF OFF OFF
5th
Disabled Disabled
ON OFF OFF OFF OFF
6th
Disabled
ON OFF OFF OFF OFF OFF
7th ON OFF OFF OFF OFF OFF OFF
Note When several terminals simultaneously turn ON,
priority is given to the terminal with the smallest
number.
“Disabled” in the above table indicates that speed is
selected regardless of ON/OFF status.
SF1
SF2
SF3
SF4
FW
1st
2nd
3rd
4th
5th
6th
7th
0th
1st
SF5
SF6
SF7
SF8
Frequency from the
Digital Operator or
the external analog
input terminal