6 - 9
6 Vector Control
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
6-2 Sensorless Vector Control
6
6-2-3 Auto-tuning of Motor Parameters
4
Operations after auto-tuning
After normal completion of auto-tuning, set the 1st Motor Parameter selection (H002) to 01
(Auto-tuning).
This enables the 1st/2nd motor parameters (H030 to H034/H230 to H234) set by the
auto-tuning function.
At the end of auto-tuning, the inverter automatically resets the Auto-tuning Selection (H001) to
00 (Disabled).
To retry auto-tuning, set H001 again to enable auto-tuning.
During auto-tuning without motor rotation, the Motor Parameter Io (No-load current) and
Motor Parameter J (Moment of inertia J) values are not measured. Set the following
parameters at the end of auto-tuning.
Precautions for Correct UsePrecautions for Correct Use
To operate the inverter with the auto-tuned data after normal completion of auto-tuning, be
sure to change the 1st Motor Parameter selection (H002) setting to 01.
Adjust the DC Injection Braking Selection (A051) and Output Voltage Gain (A045) values
according to the user environment.
1st/2nd Motor Parameter Io (H033/H233): Measure and set the no-load current of the
single motor at 50 Hz in advance.
Alternatively, check the no-load current of the
motor at 50 Hz with the motor manufacturer
and set it.
1st/2nd Motor Parameter J (H034/H234): Calculate and set the motor-shaft conversion
of the moment of inertia of the load machine.
Parameter No. Function name Data Default data Unit
H002/H202
1st/2nd Motor Parameter
selection
00: Standard motor parameter
01: Auto-tuning
02: Auto-tuning (Online auto-tuning
enabled)
00
H030/H230
1st/2nd Motor Parameter
R1 (Auto-tuning Data)
0.001 to 9.999
10.00 to 65.53
Dependent
on motor
capacity
Ω
H031/H231
1st/2nd Motor Parameter
R2 (Auto-tuning Data)
H032/H232
1st/2nd Motor Parameter
L (Auto-tuning Data)
0.01 to 99.99
100.0 to 655.3
mH
H033/H233
1st/2nd Motor Parameter
lo (Auto-tuning Data)
A
H034/H234
1st/2nd Motor Parameter J
(Auto-tuning Data)
0.001 to 9.999
10.00 to 99.99
100.0 to 999.9
1000. to 9999.
kg/m
2
A045 Output Voltage Gain 20. to 100. 100. %
A051
DC Injection Braking
Selection
00: Disabled
01: Enabled
02: Enabled (Operates only at set
frequency)
00