• To operate the inverter with the auto-tuned data after normal completion of auto-tuning, be
sure to change the 1st Motor Parameter selection (H002) setting to 01.
• Adjust the DC Injection Braking Selection (A051) and Output Voltage Gain (A045) values
according to the user environment.
5
Operations in case of error
If auto-tuning is aborted by an error, review the preset parameters and check the rated motor
torque ratio of the inverter to that of the motor. If the load is too heavy, disconnect the load and
retry auto-tuning.
If the error persists or auto-tuning is still aborted, enter the motor parameter values directly.
For details, refer to 6-2-4 Motor Parameter Settings on page 6-11.
Parameter No. Function name Data Default data Unit
H002
1st Motor Parameter
selection
00: Standard motor parameter
01: Auto-tuning
02: Auto-tuning (Online auto-tuning
enabled)
00 –
H030
1st Motor Parameter R1
(Auto-tuning Data)
0.001 to 9.999
10.00 to 65.53
Dependent
on motor
capacity
Ω
H031
1st Motor Parameter R2
(Auto-tuning Data)
H032
1st Motor Parameter L
(Auto-tuning Data)
0.01 to 99.99
100.0 to 655.3
mH
H033
1st Motor Parameter lo
(Auto-tuning Data)
A
H034
1st Motor Parameter J
(Auto-tuning Data)
0.001 to 9.999
10.00 to 99.99
100.0 to 999.9
1000. to 9999.
kg/m
2
A045 Output Voltage Gain 20. to 100. 100. %
A051
DC Injection Braking
Selection
00: Disabled
01: Enabled
02: Enabled (Operates only at set
frequency)
00 –