7-1 Monitor Mode (Group d)
7
Generally, the forward rotation is defined as the direction in which the motor rotates counterclockwise
when viewed from the shaft.
Use this function to display the PID feedback value when the PID Selection (A071) is set to 01
(Enabled) or 02 (Reverse output enabled).
The monitor value can be converted by setting the PID Scale (A075) as follows.
d004 = PID Feedback value [%] x PID Scale (A075)
The value of A075 can be set to 0.01 to 99.99 (in increments of 0.01).
Use this function to display the input status of each multi-function input terminal, based on whether the
corresponding 7-segment LED is lit or not lit.
The terminal for which the built-in CPU detected the input of a signal is indicated as ON.
Note that this is not affected by the NO/NC contact setting.
(Example)
FW and Multi-function input terminals S7, S2, S1: ON
Multi-function input terminals S8, S6, S5, S4, S3: OFF
PID Feedback Value Monitor [d004]
Parameter No. Function name Data Default data Unit
d004
PID Feedback Value
Monitor
0.00 to 99.99 (Displayed in increments of
0.01)
100.0 to 999.9 (Displayed in increments
of 0.1)
1000. to 9999. (Displayed in increments
of 1)
1000 to 9999 (10000 to 99990)
(Displayed in increments of 10)
Γ100 to Γ999 (100000 to 999000)
(Displayed in increments of 1000,
enabled when the PID function is
selected)
––
Multi-function Input Monitor [d005]