7 Detailed Functions
7 - 20
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
Set the maximum frequency to the maximum motor rotation speed or lower.
Parameter No. Function name Data Default data Unit
A004 1st Maximum Frequency 30. to 400.
60. Hz
A204
2nd Maximum Frequency
*1
*1. To enable the switching to the 2nd/3rd control, allocate one of the Multi-function Input S1 to S8 Selection (C001
to C008) to 08 (SET) or 17 (SET3) and turn ON that terminal.
30. to 400.
A304
3rd Maximum Frequency
*1
30. to 400.
Related functions A003, A203, A303, A081, A082
Output voltage
Motor rated
voltage
selection
(A082)
Base frequency Max. frequency
(A004/A204/A304)