7 Detailed Functions
7 - 22
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
• When 16 (AT: analog input switching) is allocated to a multi-function input terminal
Setting
in A005
Setting in A006
Multi-function
input
16: Terminal AT
(Analog input
switching)
Frequency
reference input
terminal
Auxiliary
frequency
reference input
terminal
Reversibility
Enabled/
Disabled
00
00 or 03
OFF FV-FC Disabled Disabled
ON FI-FC Disabled Disabled
01 (Example 1)
OFF FV-FC FE-FC Disabled
ON FI-FC FE-FC Disabled
02 (Example 2)
OFF FV-FC FE-FC Enabled
ON FI-FC FE-FC Enabled
01
00 or 03
OFF FV-FC Disabled Disabled
ON FE-FC Disabled Enabled
01 (Example 1)
OFF FV-FC FE-FC Disabled
ON FE-FC Disabled Enabled
02 (Example 2)
OFF FV-FC FE-FC Enabled
ON FE-FC Disabled Enabled
02
00 or 03
OFF FV-FC Disabled Disabled
ON Volume adjuster Disabled Disabled
01 (Example 1)
OFF FV-FC FE-FC Disabled
ON Volume adjuster Disabled Disabled
02 (Example 2)
OFF FV-FC FE-FC Enabled
ON Volume adjuster Disabled Disabled
03
00 or 03
OFF FI-FC Disabled Disabled
ON Volume adjuster Disabled Disabled
01 (Example 1)
OFF FI-FC FE-FC Disabled
ON Volume adjuster Disabled Disabled
02 (Example 2)
OFF FI-FC FE-FC Enabled
ON Volume adjuster Disabled Disabled
04
00 or 03
OFF FE-FC Disabled Enabled
ON Volume adjuster Disabled Disabled
01 (Example 1)
OFF FE-FC Disabled Enabled
ON Volume adjuster Disabled Disabled
02 (Example 2)
OFF FI-FC Disabled Enabled
ON Volume adjuster Disabled Disabled