EasyManua.ls Logo

Omron RX Series - Page 348

Omron RX Series
688 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7 Detailed Functions
7 - 22
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
When 16 (AT: analog input switching) is allocated to a multi-function input terminal
Setting
in A005
Setting in A006
Multi-function
input
16: Terminal AT
(Analog input
switching)
Frequency
reference input
terminal
Auxiliary
frequency
reference input
terminal
Reversibility
Enabled/
Disabled
00
00 or 03
OFF FV-FC Disabled Disabled
ON FI-FC Disabled Disabled
01 (Example 1)
OFF FV-FC FE-FC Disabled
ON FI-FC FE-FC Disabled
02 (Example 2)
OFF FV-FC FE-FC Enabled
ON FI-FC FE-FC Enabled
01
00 or 03
OFF FV-FC Disabled Disabled
ON FE-FC Disabled Enabled
01 (Example 1)
OFF FV-FC FE-FC Disabled
ON FE-FC Disabled Enabled
02 (Example 2)
OFF FV-FC FE-FC Enabled
ON FE-FC Disabled Enabled
02
00 or 03
OFF FV-FC Disabled Disabled
ON Volume adjuster Disabled Disabled
01 (Example 1)
OFF FV-FC FE-FC Disabled
ON Volume adjuster Disabled Disabled
02 (Example 2)
OFF FV-FC FE-FC Enabled
ON Volume adjuster Disabled Disabled
03
00 or 03
OFF FI-FC Disabled Disabled
ON Volume adjuster Disabled Disabled
01 (Example 1)
OFF FI-FC FE-FC Disabled
ON Volume adjuster Disabled Disabled
02 (Example 2)
OFF FI-FC FE-FC Enabled
ON Volume adjuster Disabled Disabled
04
00 or 03
OFF FE-FC Disabled Enabled
ON Volume adjuster Disabled Disabled
01 (Example 1)
OFF FE-FC Disabled Enabled
ON Volume adjuster Disabled Disabled
02 (Example 2)
OFF FI-FC Disabled Enabled
ON Volume adjuster Disabled Disabled

Table of Contents