7 - 57
7 Detailed Functions
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
7-3 Basic Functions (Group A)
7
Use this function to set the acceleration/deceleration pattern for each system.
Select the acceleration/deceleration pattern in the Acceleration Pattern Selection (A097)/
Deceleration Pattern Selection (A098).
The acceleration pattern and the deceleration pattern can be set independently.
These acceleration/deceleration pattern settings are effective also for frequency reference via analog
input terminals.
*1 The default data was changed from the previous model.
Acceleration/Deceleration Pattern
Parameter No. Function name Data Default data Unit
A097
Acceleration Pattern
Selection
00: Line
01: S-shape curve
02: U-shape curve
03: Inverted U-shape curve
04: EL-S-shape curve
01
*1
A098
Deceleration Pattern
Selection
A131
Acceleration Curve
Parameter
01 (Small curve) to 10 (Large curve) 02
A132
Deceleration Curve
Parameter
A150
EL-S Shape
Acceleration Curve
Ratio 1
0. to 50.
10
*1
%
A151
EL-S Shape
Acceleration Curve
Ratio 2
A152
EL-S Shape
Deceleration Curve
Ratio 1
0. to 50.
10
*1
%
A153
EL-S Shape
Deceleration Curve
Ratio 2