7 - 73
7 Detailed Functions
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
7-4 Detailed Functions (Group b)
7
If the set overload limit level is reached during acceleration, the inverter decreases the output
frequency according to the overload limit parameter.
This decrease in the frequency causes the motor decelerate, which may results in an
overvoltage.
b022 Overload Limit Level
Heavy
load (CT)
0.20 x Rated current to
2.00 x Rated current (0.4 to 55 kW)
Rated
current x 1.5
A
0.20 x Rated current to
1.80 x Rated current (75 to 132 kW)
b025
Overload Limit Level
2
Light
load (VT)
0.20 x Rated current to
1.50 x Rated current
Rated
current x 1.2
b023
Overload Limit
Parameter
0.10 to 30.00 1.0 s
b026
Overload Limit
Parameter 2
Related functions C001 to C008, C021 to C025, C026
Parameter
No.
Function name Data Default data Unit