7 Detailed Functions
7 - 126
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
Set the multi-function output P1 to P5 terminals and the multi-function relay output (MA, MB) terminal
to output specifications either of NO (Normally open contact) or NC (Normally closed contact)
individually.
The multi-function output P1 to P5 terminals are for open collector output.
The RUN signal is output from the multi-function output P1 to P5 terminals and the multi-function
relay output (MA, MB) terminal during operation.
Allocate one of the Multi-function Output P1 to P5 Selection (C021 to C025) or the Multi-function
Relay Output (MA, MB) Function Selection (C026) to 00 (RUN).
This signal is also output when DC injection braking is active.
The RUN signal is output even when the inverter does not output because the frequency reference is
0 Hz, as long as the RUN command is ON.
The timing diagram is as follows.
The inverter outputs the RUN signal until the motor is stopped even if the RUN command (FW) turns
OFF.
Multi-function Output Operation Selection
Parameter No. Function name Data Default data Unit
C031
Multi-function Output P1
Operation Selection
00: NO (Normally open contact)
01: NC (Normally closed contact)
00
C032
Multi-function Output P2
Operation Selection
C033
Multi-function Output P3
Operation Selection
C034
Multi-function Output P4
Operation Selection
C035
Multi-function Output P5
Operation Selection
C036
Multi-function Relay
Output (MA, MB)
Function Selection
00: NO contact between MA and MC,
NC contact between MB and MC
01: NC contact between MA and MC,
NO contact between MB and MC
01
Signal during RUN (RUN)
Parameter No. Function name Data Default data Unit
C021 to C025
Multi-function Output P1
to P5 Selection
00: RUN (Signal during RUN)
––
C026
Multi-function Relay
Output
(MA, MB)
Function Selection
05
Output frequency
FW
ON
ON
OFF
OFF
RUN