7 Detailed Functions
7 - 136
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
This signal will be output when the output current falls to or below the Low Current Detection Level
(C039).
In the Low Current Signal Output Mode (C038), select whether to enable the function during
acceleration and constant speed or only during constant speed.
Set the Multi-function Output P1 to P5 Selection (C021 to C025) or the Multi-function Relay Output
(MA, MB) Function Selection (C026) to 43 (LOC) to enable this function.
Low Current Signal (LOC)
Parameter
No.
Function
name
Data Default data Unit
C021 to
C025
Multi-function
Output P1 to
P5 Selection
43: LOC (Low current signal)
C026
Multi-function
Relay Output
(MA, MB)
Function
Selection
05
C038
Low Current
Signal Output
Mode
00: Enabled during acceleration/deceleration and
constant speed
01: Enabled only during constant speed
*1
*1. When the Frequency Reference Selection (A001) is set to 01 (Control circuit terminal block), the signal may not
be judged as a constant speed depending on the sampling condition. In this case, set C038 to 00 (Enabled
during acceleration/deceleration and constant speed) or increase the value set in the Analog Input Filter (A016).
01
C039
Low Current
Detection Level
Heavy
load (CT)
0.00 to 2.00 x Rated current (0.4 to 55 kW)
Rated current
value
A
0.00 to 1.80 x Rated current (75 to 132 kW)
Light
load (VT)
0.00 to 1.50 x Rated current
Rated current
value
A
Output current [A]
Low Current
Detection Level
(C039)
Low current
signal (LOC)
ON
ON