7 Detailed Functions
7 - 142
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
• The digital terminal AM/AMI on the control circuit terminal block enables the monitoring of the output
frequency and the output current.
The terminal AM provides an analog output of 0 to 10 V.
The terminal AMI provides an analog output of 0 to 20 mA. By default, this terminal is set to provide
an analog output of 4 to 20 mA.
Select the signal you want to output from the following table.
Analog Output AM/AMI Terminals
AM/AMI Selection
Parameter No. Function name
Data Description Full-scale value
C028/C029
AM
Selection/
AMI
Selection
00
Output frequency
*1
*1. 00 (Output frequency) represents a frequency value that takes into account the aspects of vector control
compensation (such as sensorless vector control) and even stabilization control.
07 (LAD frequency) represents the frequency commanded by the inverter and is equivalent of the Output
Frequency Monitor (d001) value.
0 to Maximum frequency (Hz)
*2
*2. When Sensor vector control is selected (A044 = 05), the real frequency (detected frequency) will be displayed.
01 Output current 0% to 200%
02
Output torque
*3
*3. This signal will be output only when Sensorless vector control, 0-Hz sensorless vector control, or Sensor vector
control is selected in Control Method (V/f Characteristics) on page 7-34.
*4. The specifications of the output torque (signed) are as follows.
In the above example,
· When AM Gain Setting (C106) = 100%, AM output = 10 V at torque output of 100%, and
· When AM Gain Setting (C106) = 50%, AM output = 7.5 V at torque output of 100%.
*5. For functional details, refer to “DriveProgramming User’s Manual (I580)”.
0% to 200%
04 Output voltage 0% to 100%
05 Input power 0% to 200%
06 Electronic thermal load rate 0% to 100%
07
LAD frequency
*1
0 to Maximum frequency [Hz]
09 Motor temperature 0 to 200°C (0°C output at 0°C or lower)
10 Cooling fin temperature 0 to 200°C (0°C output at 0°C or lower)
11
Output torque (signed)
*3
AM output only
0% to 200%
*4
(C028 only)
13
DriveProgramming (YA(1))
*5
AM output only
0% to 100% (C028 only)
14
DriveProgramming (YA(2))
*5
AM output only
0% to 100% (C029 only)
19 Option 1 –