7 Detailed Functions
7 - 144
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
Use these parameters to set the output gain of the inverter according to the meter connected to the
terminal AM/AMI.
(Example) If AMI provides an output of 4 to 20 mA: C110 = 4 ÷ 20 = 20 [%] (Default data)
The relationship between the AM Gain Setting (C106) and the AM Bias Setting (C109) when there
values are changed is as follows.
Note The relationship between the AMI Gain Setting (C106) and the AMI Bias Setting (C110) is similar to this.
AM/AMI Gain Setting
Parameter No. Function name Data Default data Unit
C106 AM Gain Setting
50. to 200.
Set AM monitor gain.
100.
%
C107 AMI Gain Setting
50. to 200.
Set AMI monitor gain.
C109 AM Bias Setting
0. to 100.
Set AM monitor offset.
0.
C110 AMI Bias Setting
0. to 100.
Set AMI monitor offset.
20.
C109 = 0 (Offset 0%) C109 = 50 (Offset 50%)
AM output
(AMI output)
Full-scale
1/2
Full-scale
C106=200%
(C107=200%)
C106=100%
(C107=100%)
C106=50%
(C107=50%)
C109=0%
(C110=0%)
Select
monitor
value
AM output
(AMI output)
Full-scale
1/2
Full-scale
C106=200%
(C107=200%)
C106=100%
(C107=100%)
C106=50%
(C107=50%)
C109=50%
(C110=50%)
Select
monitor
value