8 Communications Functions
8 - 50
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
133C to
133E hex
– Not used – – – –
133F hex 133E hex
Window Comparator FV
Upper Limit Level
b060 R/W
Set an upper limit level.
Setting range: 0 to 100
Lower limit: Lower limit level +
Hysteresis width x 2
1 [%]
1340 hex 133F hex
Window Comparator FV
Lower Limit Level
b061 R/W
Set a lower limit level.
Setting range: 0 to 100
Upper limit: Upper limit level -
Hysteresis width x 2
1 [%]
1341 hex 1340 hex
Window Comparator FV
Hysteresis Width
b062 R/W
Set a hysteresis width for the
upper and lower limit levels.
Setting range: 0 to 10
Upper limit: (Upper limit level –
Lower limit level) / 2
1 [%]
1342 hex 1341 hex
Window Comparator FI Upper
Limit Level
b063 R/W
Set an upper limit level.
Setting range: 0 to 100
Lower limit: Lower limit level +
Hysteresis width x 2
1 [%]
1343 hex 1342 hex
Window Comparator FI Lower
Limit Level
b064 R/W
Set an lower limit level.
Setting range: 0 to 100
Upper limit: Upper limit level -
Hysteresis width x 2
1 [%]
1344 hex 1343 hex
Window Comparator FI
Hysteresis Width
b065 R/W
Set an hysteresis width for the
upper and lower limit levels.
Setting range: 0 to 10
Upper limit: (Upper limit level –
Lower limit level) / 2
1 [%]
1345 hex 1344 hex
Window Comparator FE
Upper Limit Level
b066 R/W
Set an upper limit level.
Setting range: –100 to 100
Lower limit: Lower limit level +
Hysteresis width x 2
1 [%]
1346 hex 1345 hex
Window Comparator FE
Lower Limit Level
b067 R/W
Set a lower limit level.
Setting range: –100 to 100
Upper limit: Upper limit level -
Hysteresis width x 2
1 [%]
1347 hex 1346 hex
Window Comparator FE
Hysteresis Width
b068 R/W
Set a hysteresis width for the
upper and lower limit levels.
Setting range: 0 to 10
Upper limit: (Upper limit level –
Lower limit level) / 2
1 [%]
1348 hex – Not used – – – –
1349 hex 1348 hex
Analog Operation Level at FV
Disconnection
b070 R/W
0 to 100
255 (no)
1 [%]
134A hex 1349 hex
Analog Operation Level at FI
Disconnection
b071 R/W
0 to 100
255 (no)
1 [%]
134B hex 134A hex
Analog Operation Level at FE
Disconnection
b072 R/W
–100 to 100
127
(no)
1 [%]
134C to
1350 hex
– Not used – – – –
Register
No.
Modbus
register
spec. No.
Function name
Parameter
No.
R/W Monitor or setting data
Resolution