8 Communications Functions
8 - 52
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
1365 hex 1364 hex Thermistor Selection b098 R/W
00: Disabled
01: PTC enabled
02: NTC enabled
1366 hex 1365 hex Thermistor Error Level b099 R/W 0 to 9999 1 [Ω]
1367 hex 1366 hex Free V/f Frequency 1 b100 R/W 0 to Free V/f Frequency 2 1 [Hz]
1368 hex 1367 hex Free V/f Voltage 1 b101 R/W 0 to 8000 0.1 [V]
1369 hex 1368 hex Free V/f Frequency 2 b102 R/W
Free V/f Frequency 1 to Free V/f
Frequency 3
1 [Hz]
136A hex 1369 hex Free V/f Voltage 2 b103 R/W 0 to 8000 0.1 [V]
136B hex 136A hex Free V/f Frequency 3 b104 R/W
Free V/f Frequency 2 to Free V/f
Frequency 4
1 [Hz]
136C hex 136B hex Free V/f Voltage 3 b105 R/W 0 to 8000 0.1 [V]
136D hex 136C hex Free V/f Frequency 4 b106 R/W
Free V/f Frequency 3 to Free V/f
Frequency 5
1 [Hz]
136E hex 136D hex Free V/f Voltage 4 b107 R/W 0 to 8000 0.1 [V]
136F hex 136E hex Free V/f Frequency 5 b108 R/W
Free V/f Frequency 4 to Free V/f
Frequency 6
1 [Hz]
1370 hex 136F hex Free V/f Voltage 5 b109 R/W 0 to 8000 0.1 [V]
1371 hex 1370 hex Free V/f Frequency 6 b110 R/W
Free V/f Frequency 5 to Free V/f
Frequency 7
1 [Hz]
1372 hex 1371 hex Free V/f Voltage 6 b111 R/W 0 to 8000 0.1 [V]
1373 hex 1372 hex Free V/f Frequency 7 b112 R/W Free V/f Frequency 6 to 400 1 [Hz]
1374 hex 1373 hex Free V/f Voltage 7 b113 R/W 0 to 8000 0.1 [V]
1375 to
137A hex
Not used
137B hex 137A hex
Brake Control Function
Selection
b120 R/W
00: Disabled
01: Enabled
137C hex 137B hex Brake Release Wait Time b121 R/W 0 to 500 0.01 [s]
137D hex 137C hex
Acceleration Wait Time on
Brake Control
b122 R/W 0 to 500 0.01 [s]
137E hex 137D hex
Stop Wait Time on Brake
Control
b123 R/W 0 to 500 0.01 [s]
137F hex 137E hex Brake Error Detection Time b124 R/W 0 to 500 0.01 [s]
1380 hex 137F hex Brake Release Frequency b125 R/W 0 to 40000 0.01 [Hz]
1381 hex 1380 hex Brake Release Current b126 R/W
0 to 2000 (0.4 to 55 kW)
0 to 1800 (75 to 132 kW)
0.1 [%]
1382 hex 1381 hex Break Force Frequency b127 R/W 0 to 40000 0.01 [Hz]
1383 hex Not used
1384 hex Not used
1385 hex 1384 hex
Overvoltage Suppression
Function Selection During
Deceleration
b130 R/W
00: Disabled
01: Enabled (DC voltage kept
constant)
02: Enabled (Acceleration
enabled)
1386 hex 1385 hex
Overvoltage Suppression
Level During Deceleration
b131 R/W
200-V class: 330 to 390
400-V class: 660 to 780
1 [V]
Register
No.
Modbus
register
spec. No.
Function name
Parameter
No.
R/W Monitor or setting data
Resolution