8 Communications Functions
8 - 54
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
1401 hex 1400 hex
Multi-function Input S1
Selection
C001 R/W
01: RV (Reverse)
02:
CF1 (Multi-step speed setting binary 1)
03:
CF2 (Multi-step speed setting binary 2)
04:
CF3 (Multi-step speed setting binary 3)
05:
CF4 (Multi-step speed setting binary 4)
06: JG (Jogging)
07:
DB (External DC injection braking)
08: SET (2nd control)
09:
2CH (2-step acceleration/deceleration)
11: FRS (Free-run stop)
12: EXT (External trip)
13:
USP (Power recovery restart prevention function)
14: CS (Commercial switch)
15: SFT (Soft lock)
16: AT (Analog input switching)
17: SET3 (3rd control)
18: RS (Reset)
20: STA (3-wire start)
21: STP (3-wire stop)
22: FR (3-wire forward/reverse)
23: PID (PID disabled)
24: PIDC (PID integral reset)
26: CAS (Control gain switching)
27:
UP (Remote operation accelerated)
28:
DWN (Remote operation decelerated)
29: UDC (Remote data clear)
31: OPE (Forced operator function)
32:
SF1 (Multi-step speed setting bit 1)
33:
SF2 (Multi-step speed setting bit 2)
34:
SF3 (Multi-step speed setting bit 3)
35:
SF4 (Multi-step speed setting bit 4)
36:
SF5 (Multi-step speed setting bit 5)
37:
SF6 (Multi-step speed setting bit 6)
38:
SF7 (Multi-step speed setting bit 7)
39: OLR (Overload limit switching)
40:
TL (Torque limit enabled/disabled)
41: TRQ1 (Torque limit switching 1)
42: TRQ2 (Torque limit switching 2)
43: PPI (P/PI switching)
44: BOK (Brake confirmation)
45: ORT (Orientation)
46: LAC (LAD cancel)
47: PCLR (Position deviation clear)
48:
STAT: Pulse train position command permission
50:
ADD (Set frequency A145 addition)
51: F-TM (Forced terminal block)
52:
ATR (Torque command input permission)
53: KHC (Integrated power clear)
54: SON (Servo ON)
55: FOC (Preliminary excitation)
56: MI1 (General-purpose input 1)
57: MI2 (General-purpose input 2)
58: MI3 (General-purpose input 3)
59: MI4 (General-purpose input 4)
60: MI5 (General-purpose input 5)
61: MI6 (General-purpose input 6)
62: MI7 (General-purpose input 7)
63: MI8 (General-purpose input 8)
65: AHD (Analog command held)
66:
CP1 (Position command selection 1)
67:
CP2 (Position command selection 2)
68:
CP3 (Position command selection 3)
69: ORL (Zero return limit signal)
70: ORG (Zero return startup signal)
71: FOT (Forward driving stop)
72: ROT (Reverse driving stop)
73: SPD (Speed/Position switching)
74: PCNT (Pulse counter)
75:
PCC (Pulse counter clear)
82: PRG (DriveProgramming start)
255: no (No allocation)
–
1402 hex 1401 hex
Multi-function Input S2
Selection
C002 R/W –
1403 hex 1402 hex
Multi-function Input S3
Selection
C003 R/W –
1404 hex 1403 hex
Multi-function Input S4
Selection
C004 R/W –
1405 hex 1404 hex
Multi-function Input S5
Selection
C005 R/W –
1406 hex 1405 hex
Multi-function Input S6
Selection
C006 R/W –
1407 hex 1406 hex
Multi-function Input S7
Selection
C007 R/W –
1408 hex 1407 hex
Multi-function Input S8
Selection
C008 R/W –
Register
No.
Modbus
register
spec. No.
Function name
Parameter
No.
R/W Monitor or setting data
Resolution