8 Communications Functions
8 - 56
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
1415 hex 1414 hex
Multi-function Output P1
Selection
C021 R/W
00: RUN (Signal during RUN)
01:
FA1 (Constant speed arrival signal)
02:
FA2 (Set frequency exceeded signal)
03: OL (Overload warning)
04: OD (Excessive PID deviation)
05: AL (Alarm signal)
06: FA3 (Set-frequency only signal)
07:
OTQ (Overtorque/Undertorque signal)
08:
IP (Signal during power interruption)
09: UV (Signal during undervoltage)
10: TRQ (Torque limit)
11: RNT (RUN time over)
12: ONT (Power ON time over)
13:
THM (Electronic thermal warning)
19: BRK (Brake release)
20: BER (Brake error)
21: ZS (0-Hz detection signal)
22:
DSE (Excessive speed deviation)
23: POK (Position ready)
24:
FA4 (Set frequency exceeded signal 2)
25:
FA5 (Set-frequency only signal 2)
26: OL2 (Overload warning 2)
27: FVDc (Analog FV disconnection
detection)
28:
FIDc (Analog F disconnection detection)
29: FEDc (Analog FE disconnection
detection)
31:
FBV (PID feedback comparison signal)
32: NDc (Communications
disconnection detection)
33: LOG1 (Logic operation output 1)
34: LOG2 (Logic operation output 2)
35: LOG3 (Logic operation output 3)
36: LOG4 (Logic operation output 4)
37: LOG5 (Logic operation output 5)
38: LOG6 (Logic operation output 6)
39:
WAC (Capacitor life warning signal)
40:
WAF (Cooling fan life warning signal)
41: FR (Starting contact signal)
42:
OHF (Cooling fin overheat warning)
43: LOC (Low current signal)
44:
MO1 (General-purpose output 1)
45:
MO2 (General-purpose output 2)
46:
MO3 (General-purpose output 3)
47:
MO4 (General-purpose output 4)
48:
MO5 (General-purpose output 5)
49:
MO6 (General-purpose output 6)
50: IRDY (Operation ready)
51: FWR (Forward run signal)
52: RVR (Reverse run signal)
53: MJA (Fatal fault signal)
54: WCFV (Window comparator FV)
55: WCFI (Window comparator FI)
56: WCFE (Window comparator FE)
63: OPO (Option)
255: no (No allocation)
(When an alarm code is selected in
C062, multi-function output
terminals P1 to P3 or P1 to P4 are
force-set to output an alarm code
(AC0 to AC2 or AC0 to AC3).)
–
1416 hex 1415 hex
Multi-function OutputP2
Selection
C022 R/W –
1417 hex 1416 hex
Multi-function OutputP3
Selection
C023 R/W –
1418 hex 1417 hex
Multi-function OutputP4
Selection
C024 R/W –
1419 hex 1418 hex
Multi-function OutputP5
Selection
C025 R/W –
141A hex 1419 hex
Multi-function Relay Output
(MA, MB) Function Selection
C026 R/W –
Register
No.
Modbus
register
spec. No.
Function name
Parameter
No.
R/W Monitor or setting data
Resolution