8 Communications Functions
8 - 76
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
Group A/b/C/H/P
Register
No.
Modbus
register
spec. No.
Function name
Parameter
No.
R/W Monitor or setting data
Resolution
3203 hex 3202 hex 3rd Base Frequency A303 R/W 30 to 3rd Maximum Frequency 1 [Hz]
3204 hex 3203 hex 3rd Maximum Frequency A304 R/W 30 to 400 1 [Hz]
3205 to
3215 hex
– Not used – – – –
3216 hex 3215 hex
3rd Multi-step Speed
Reference 0
A320
(HIGH)
R/W
0
Starting Frequency to 3rd
Maximum Frequency
0.01 [Hz]
3217 hex 3216 hex
A320
(LOW)
R/W
3218 to
323B hex
– Not used – – – –
323C hex 323B hex
3rd Manual Torque Boost
Voltage
A342 R/W 0 to 200 0.1 [%]
323D hex 323C hex
3rd Manual Torque Boost
Frequency
A343 R/W 0 to 500 0.1 [%]
323E hex 323D hex 3rd Control Method A344 R/W
00: Constant torque
characteristics
01: Reduced torque
characteristics
–
323F to
326C hex
– Not used – – – –
326D hex 326C hex
3rd Acceleration Time 2
A392
(HIGH)
R/W
1 to 360000 0.01 [s]
326E hex 326D hex
A392
(LOW)
R/W
326F hex 326E hex
3rd Deceleration Time 2
A393
(HIGH)
R/W
1 to 360000 0.01 [s]
3270 hex 326F hex
A393
(LOW)
R/W
3271 to
330B hex
– Not used – – – –
330C hex 330B hex 3rd Electronic Thermal Level b312 R/W 200 to 1000 0.1 [%]
330D hex 330C hex
3rd Electronic Thermal
Characteristics Selection
b313 R/W
00: Reduced torque
characteristics
01: Constant torque
characteristics
02: Free setting
–
330E to
3506 hex
– Not used – – – –
3507 hex 3506 hex 3rd Stabilization Parameter H306 R/W 0 to 255 1
3508 hex
to
– Not used – – – –