9 Overview of DriveProgramming
9 - 2
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
9-1 Overview of DriveProgramming
The 3G3RX-V1 Series Inverter has the buit-in simple sequence function (DriveProgramming), which
enables a stand-alone inverter to perform simple sequence control.
You can create programs easily by using the CX-Drive. The user programs you created can be
downloaded onto the inverter for programmed inverter operation.
The DriveProgramming supports both flowchart and text language method programming.
Five tasks can be processed in parallel.
User programs can be executed externally by the ON/OFF signal input via a multi-function input
terminal.
The user programs can be used to read and write functions allocated to the multi-function input and
output terminals.
The Digital Operator enables you to change the settings of the output frequency,
acceleration/deceleration time, and other parameters that require on-site adjustment by specifying
the user parameters (P100 to P131), without connecting the computer.
Because user programs are stored in the internal EEPROM of the inverter, you can start a program
immediately after the inverter power supply is turned on.
Connecting the optional LCD Digital Operator enables the control of the inverter by using the LCD
Digital Operator’s clock command.
Precautions for Safe Use
If the clock command is used in the DriveProgramming, an unexpected operation may occur
due to weak battery of the LCD Digital Operator. Take measures such as detecting a weak
battery by a check that the clock data returns to the initial setting and stopping the inverter or
programs. When the LCD Digital Operator is removed or disconnected, DriveProgramming is
in a waiting status by the clock command.
If the DriveProgramming stops during multi-function output, the output status is held. Take
safety precautions such as stopping peripheral devices.