EasyManua.ls Logo

Omron RX Series - Page 87

Omron RX Series
688 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 - 31
2 Design
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
2-3 Wiring
2
2-3-4 Wiring for Main Circuit Terminals
Installing earth leakage breaker
When selecting the earth leakage breaker to use between the power supply and the main power
supply input terminals (R/L1, S/L2, T/L3), consider the following two points.
High-frequency leakage current from inverter
The inverter produces a high-frequency leakage current due to its high-speed output switching.
In general, a leakage current of approximately 100 mA will flow for the power cable length of 1 m per
inverter. Moreover, an additional leakage current of approximately 5 mA will flow with the increasing
length by 1 m.
Therefore, an earth leakage breaker to use in the power input section must be dedicated for the
inverter, which removes high-frequency leakage current and detects only the leakage current in a
frequency range that is dangerous to the human body.
Select a special earth leakage breaker for the inverter with a sensitivity current rating of 10 mA or
higher per inverter.
If you use a general earth leakage breaker (which detects high-frequency leakage current), select
one with a sensitivity current rating of 200 mA or higher per inverter and an operation time of 0.1 s
or longer.
Leakage current from EMC noise filter
The EMC noise filter is designed to comply with European CE standards.
Specifically, it is designed to meet the neutral-point grounding requirement of the European power
supply specifications.
Therefore, using the EMC noise filter with the phase S grounding causes an increase of leakage
current.
For use with the phase S grounding, it is recommended to use the Input Noise Filter (Model:
3G3AX-NFI).
Check the maximum leakage current value in the standard built-in EMC filter specifications for
3G3RX Series.
Check also the maximum leakage current value in the optional external EMC noise filter
specifications.
Installing magnetic contactor
To shut off the main circuit power supply with a sequence, you can use a magnetic contactor (MC)
on the inverter side closer than a molded case circuit-breaker (MCCB).
However, do not run or stop the inverter by turning ON/OFF a magnetic contactor.
Use the RUN command signal (FW/RV) via the control circuit terminal of the inverter.
Construct a sequence that turns OFF the power supply via the alarm output signal of the inverter.
To use one or more braking resistors/regenerative braking units, construct a sequence that turns
OFF a magnetic contactor via a thermal relay contact in each unit.
Precautions for Correct UsePrecautions for Correct Use
Do not shut off the power supply more than once in 3 minutes. Doing so may result in an inverter
damage.

Table of Contents

Related product manuals