Commission
ing the fire brigade periphery module FCI2001
-
D1
26
112 | 188
Building Technologies
009052_s_en_
--
Fire Safety
2016
-
-
02
26 Commissioning the fire brigade periphery
module FCI2001-D1
The fire brigade periphery module FCI2001-D1 monitors the monitored inputs and
outputs for short-circuit and open line. The resistance values of the lines may be
read in and stored at the push of a button. If a deviation from the quiescent value is
detected, the control panel evaluates a short-circuit or an open line.
The following table shows the monitored inputs and outputs:
Terminal Pin Function
X4 4, 5 and 1, 2
Remote transmission or transmission device (RT
Alarm) and release element ('FSE')
X5 7, 8 'Key depot' (tamper monitoring)
X6 5, 6 Local alarm
Figure 6: View of the fire brigade periphery module
X4–X6 Connection terminals
S101 Button
Procedure
1. Check the connected lines for short-circuit and open line.
2. Connect the lines.
During the commissioning of the control panel, fault messages are
indicated, provided that there are any deviations from the basic settings.
3. Press the push-button S101.
The resistance values are read in.
S101
X5 X6X4